![](https://static.wixstatic.com/media/9fae93_b95d7ac3db15404eb74cfabebf7bd574~mv2.png/v1/crop/x_0,y_39,w_430,h_170/fill/w_276,h_90,al_c,q_85,usm_0.66_1.00_0.01,enc_avif,quality_auto/9fae93_b95d7ac3db15404eb74cfabebf7bd574~mv2.png)
Universal Voltage Relay Type SW32V
Universal-Voltage-Relay for monitoring of over- and undervoltage in DC-, AC- and 3-phase-voltages incl. monitoring of phasesymmetry and phase-sequence
Product description
The SW32V voltage relay is a high-quality voltage monitor with a large measurement range for monitoring direct, alternating and three-phase networks for overvoltage and/or undervoltage. In three-phase current networks, phase symmetry and phase sequence can be monitored in addition.
The limits are set in volts. That allows using the unit with various rated voltages.The digital display is used to display the measurements and to precisely set limits, response times and functions.
Summary of the functions
For use as a voltage monitor in energy generation and distribution plants, especially in-plant systems such as PV plants or combined heat and power plants. Voltage monitoring in machines and plants to prevent errors, damage or failures in sensitive equipment or devices.
-
Voltage monitoring in direct current networks DC 10.0…600 V
-
Voltage monitoring in alternating current networks AC 15.0…480 V
-
Voltage monitoring in three-phase current networks with//without N up to 3AC 830 V
-
Preset programs for grid- and plant protection according to bdew directive (medium voltage)
-
Asymmetrical and phase failure monitoring connectable
-
Real root mean square measurement (for AC, both half waves)
-
2 Alarms/output relays, 1 each change-over contact
-
Alarm and reset delay for every limit value can be individually set
-
Setting of limits and hysteresis in volts
-
Measurement value simulation to check the settings
-
Code lock can be enabled
-
Control voltage AC/DC 24-270 V
-
Distributor housing for panel mounting, 4 TE (70 mm), front-to-back size 55 mm
-
Mounting on 35 mm mounting rails DIN EN 60715
Technical Data
Control voltage Us
Rated connection ....... AC/DC 24-270 V, 0/45...65 Hz, < 5 VA
DC: 20.4...297 V, AC: 20.4...297 V
Output relay (2 x change-over contact)
Switching voltage ....... Max. AC 415 V
Switching capacity ...... 5 A 250 V
max. AC cos φ = 1
Switching capacity
max. DC (resistive) ....... 0.3 A DC 300 V ..... 5 A DC 30 V
Nominal operational current Ie ....... AC-15 Ie = 3 A Ue = 250 V
DC-13 Ie = 2 A Ue = 24 V
DC-13 Ie = 0.4 A Ue = 120 V
DC-13 Ie = 0.2 A Ue = 250 V
Recommended series fuse ....... max. T 3.15 A (gL)
Contact service life, mech. ....... 30 x 106 operating cycles
Contact service life,
electr. cos φ = 1 ....... 5 x 105 operating cycles at AC 250 V / 3 A
Voltage measurement
Measurement voltage DC ....... DC 10.0…600V
Measurement voltage
phase – phase ....... AC 26.0…830 V (< 5V: 0 is displayed)
Measurement voltage
phase – N ....... AC 15.0…480 V (< 5V: 0 is displayed)
Frequency AC measurement ....... 40…100 Hz
Measurement time DC ....... DC Mean value over 50ms
Measurement time AC ....... < 50ms
Measurement accuracy DC ....... 0.5% of measurement ± 1 digit
Measurement accuracy AC ....... > 100V: 0.8% of measurement ± 1 digit
(with N) < 100V: 0.8% of measurement ± 5 digits (res. 0.1V)
Measurement accuracy AC ....... > 100V: 1.0% of measurement ± 1 digit
(without N) < 100V: 1.0% of measurement ± 5 digits (res. 0.1V)
Measurement principle ....... Real root mean square measurement
(both half waves)
Hysteresis ....... Adjustable 1…99 V
Accuracy asymmetry ....... ± Asymmetry in % * 0.15
Hysteresis asymmetry ....... Fixed 1%
Measuring functions ....... 3-phase with/without N, 1-phase against N,
DC
Response time ....... Adjustable 0.05 (±15ms)…99.9 s
Reset time ....... Adjustable 0(>200ms) … 999 s
Test conditions (EN 60255)
Rated impulse ....... 6000 V
withstand vltage
Overvoltage category ....... III
Pollution degree ....... 2
Rated insulation voltage Ui ....... AC 690 V
Operating time ....... 100 %
Permissible
ambient temperature ....... -20 °C... +55 °C EN 60 068-2-2 dry heat
EMC - immunity ....... EN 61000-6-2
EMC - emission ....... EN 61000-6-4
Housing
Mounting type ....... V4
Front-to-back size ....... 55 mm
Dimensions (W x H x D) ....... 90 x 70 x 58 mm
Wiring connection
single strand ....... ea. 1 x 4 mm2
Finely stranded with
wire end ferrule ....... ea. 1 x 2.5 mm2
Protection class, housing ....... IP 30
Protection class, terminals ....... IP 20
Mounting ....... Snap-on fastening on 35 mm mounting rail acc EN 60 715 or with M4 screwed attachment (additional bar not included in the scope of delivery)
Weight ....... approx. 200 g
For requested more information